Application of Acrel-6000 Electrical Fire Monitoring System in Suzhou North Ring Road Tunnel
2019-12-25 13:03:22
This paper briefly describes the composition principle of the electrical fire monitoring system, and analyzes the design basis and related specifications of the electrical fire monitoring system in the application. Finally, through the introduction of Ankerui residual current electric fire monitoring system in the Suzhou North Ring Road Tunnel Project, the realization of the function of the electrical fire monitoring system and its significance are expounded.
Yang Junjun An Kerui Electric Co., Ltd. Shanghai Jiading
Summary:
0 Overview
The Suzhou North Ring Tunnel is located at the South Square of Suzhou Railway Station. The total length of the project is 928.75 meters, of which the tunnel is 725 meters long and the construction cost is about 180 million yuan. The scope of monitoring of this project is a basement substation.
There are 159 ARCM100-Z residual current meters in the R&D building of Suzhou Printing Factory, which are installed in the floor distribution box. The field instrument is connected to the Acrel-6000 piano electrical fire monitoring system of the control center by bus.
1 reference standard
In recent years, in order to increase the intensity of electrical fire monitoring and prevention, the state has successively formulated or revised a number of relevant standards and regulations to strengthen the prevention of electrical fires. There are:
1. It is GB50045-95 (2005 edition) "Code for Fire Protection Design of High-rise Civil Buildings", which stipulates in Article 9.5.1 that it is necessary to install a leakage fire alarm system in places with high fire risk and dense personnel in high-rise buildings.
2. It is GB50016-2006 "Code for Fire Protection of Building Design", which is stipulated in Article 11.2.7: The following places should be equipped with residual current action electrical fire monitoring system. These venues include various types of theaters, galleries, warehouses, residential communities, hospitals, shops, schools, and more.
3. The relevant provisions of the national standard "Building electrical fire prevention requirements and testing methods" also clearly require that "the residual current action protector that automatically cuts off the power or alarm should be set at the power incoming end".
4. The products of the electrical fire monitoring system shall meet: GB14287.1-2005 "Electrical Fire Monitoring Equipment", GB14287.2-2005 "Residual Current Electric Fire Monitoring Detector", GB14287.3-2005 "Measurement Temperature Electric Fire Monitoring and Detection" 》
5. The installation and operation of the electrical fire monitoring system shall meet the requirements of GB13955-2005 "Installation and operation of residual current action protection device"
6. The power supply of the electrical fire monitoring system shall meet the requirements of GB50052 "Design Specifications for Power Supply and Distribution Systems"
7. The design of the electrical fire monitoring system shall meet the requirements of the Design Method of Electrical Fire Monitoring System (Interim Provisions)
2 system components
The electrical fire project of Suzhou North Ring Road Tunnel consists of electrical fire monitoring background, electrical fire detector and leakage current transformer.
The communication bus of this project has access to eight communication buses, which are respectively connected to the distribution outlets of the power distribution station and are connected to the corresponding buses. After the bus is connected hand in hand in a distribution box, it is connected to the background of the piano to form the aorta of the electrical fire system. The leakage current transformer in the drawer cabinet is connected to the leakage detector through the current line, and the leakage detector displays the leakage condition in real time. The above describes a set of electrical fire monitoring systems with stable signal and reliable accuracy. The system networking is divided into three layers:
1) Station management
The management of the station control management system for the electrical fire monitoring system is the direct window of human-computer interaction and the uppermost part of the system. Mainly consists of system software and necessary hardware equipment, such as console, UPS power supply and so on. The monitoring system software calculates, analyzes, and processes various types of data information on the site, and responds to the on-site transportation situation by means of graphics, digital display, sound, and indicator lights.
Monitoring host: used for data collection, processing, and data forwarding. Provides data interfaces for system management, maintenance, and analysis within and outside the system.
UPS: Ensure the normal power supply of the computer monitoring system, and ensure the normal operation of the station management management equipment when the whole system has power supply problems.
The background monitoring device is set in the basement control room.
2) Network communication layer
Communication medium: The system mainly adopts shielded twisted pair cable, realizes real-time communication between field device and host computer by RS485 interface and MODBUS communication protocol.
3) Field device layer
The field device layer is a data acquisition terminal, mainly for the ARCM100-Z series of residual electrical fire monitoring detectors.
The system structure topology is as follows:
3 electrical fire equipment
3.1 Main equipment parameters:
a power supply
1 rated working voltage AC220V (-15% ~ +10%)
2 Backup power supply: When the main power supply is under voltage or power failure, maintain the monitoring equipment working time ≥ 30 minutes
b work system
24-hour work schedule
c communication method
RS485 bus communication, Modbus-RTU communication protocol, transmission distance of 1km, can extend the communication transmission distance through the repeater.
d monitoring capacity
1 The monitoring device can monitor up to 1024 monitoring units (detectors).
2 can be equipped with ARCM series monitoring detectors.
e monitoring alarm project
1 Residual current fault (leakage): fault unit attribute (part, type)
2 Temperature alarm (over temperature): Fault unit attribute (part, type)
3 Current fault (overcurrent): Fault unit attribute (part, type)
Monitoring alarm response time: ≤30s
Monitoring alarm sound pressure level (A weighting): ≥70db/1m
Monitoring alarm light display: red LED indicator
Monitor alarm sound signal: Manually cancel, when the alarm signal is input again, it can be started again
f fault alarm item
1 The connection between the monitoring device and the detector is open and shorted.
2 main power undervoltage or power failure
3 standby power battery short circuit, open circuit
Fault alarm response time: ≤100s
Monitoring alarm sound pressure level (A weighting): ≥70db/1m
Monitoring alarm light display: yellow LED indicator
Fault alarm sound signal: manual elimination, can be started again when there is alarm signal input again
The normal operation of the non-faulty loop is not affected during the fault
g control output
Alarm control output: normally open passive contact, capacity: AC250V 3A or DC30V 3A
h self-test project
1 Indicator check: alarm, fault, operation, main power, standby power indicator
2 monitor check
3 audio device inspection
Self-test time ≤60s
i history
1 Record content: record type, time of occurrence, detector, area, fault description.
2 Record query: Query according to the date and type of the record.
j operation rating
1 Daily duty class: real-time status monitoring, history query.
2 Monitoring operation level: real-time status monitoring, history query, remote reset of detector.
3 System management level: real-time status monitoring, history query, remote reset of detectors, remote modification of detector parameters, system parameter setting and modification of monitoring equipment, operator addition and deletion.
k use environmental conditions
1 Workplace: Fire control room, or installed side by side with fire control console
2 Working environment temperature: 0 ° C ~ 40 ° C
3 Working environment relative humidity: 5% ~ 95% RH
4 Altitude: ≤2500m
l main components
1 main control unit: industrial grade computer (CPU frequency is not lower than 2.0G, 1G and above memory), configuration keyboard, mouse and 17" liquid crystal display;
2 I/O modules: built-in ARTU remote intelligent I/O modules developed by the company;
3 sound and light alarm: built-in active speakers, LED indicators;
4 button: mute button, reset button;
5 Backup power supply: built-in 1kVA online long-acting UPS, 3 12V/24Ah maintenance-free batteries.
3.2, ARCM300 series instruments
The ARCM300 residual current electrical fire monitoring detector is designed for TT and TN systems below 0.4kV. It monitors and manages fire risk parameters such as residual current, conductor temperature, overcurrent and overvoltage in the distribution circuit. Thereby preventing the occurrence of electrical fires and real-time monitoring of various power parameters, providing accurate data for energy management. The product adopts advanced microcontroller technology, with high integration, small size, convenient installation, intelligent, digital and networked. It is an ideal choice for building electrical fire prevention monitoring and system insulation aging prediction. The product complies with the standard requirements of GB14287.2-2005 "Electrical Fire Monitoring System Part 2: Residual Current Electrical Fire Monitoring Detector".
4 system function
4.1 monitoring alarm function
The monitoring equipment can receive the leakage and temperature information of multiple detectors, and emit an audible and visual alarm signal when the alarm occurs. At the same time, the red “alarm†indicator on the cabinet lights up. The display indicates the alarm part and leakage, temperature value, record alarm time, sound and light alarm. Keep it until the detector is reset remotely by pressing the Reset button. The audible alarm signal can also be manually removed using the mute button.
4.2 control output function
When the monitored loop leakage alarm, the control output relay is closed to control the protected circuit or other equipment. When the alarm is eliminated, the control output relay is released.
4.3 fault alarm function
Communication failure alarm: When a communication failure occurs between the monitoring device and any of the connected detectors, the corresponding detector in the monitoring screen displays a fault indication, and the yellow “fault†indicator on the cabinet lights up, and a fault alarm sound is emitted. .
Power failure alarm: When the main power or backup power fails, the monitoring device also emits an audible and visual alarm signal and displays the fault information. You can enter the corresponding interface to view the detailed information and release the alarm sound.
4.4 self-test function
Check that all status indicators, displays, and audio devices in the device are working.
4.5 alarm record storage query function
When leakage, over-temperature alarm or communication or power failure occurs, the alarm part, fault information, alarm time and other information are stored in the database. When the alarm is cancelled or the fault is eliminated, the same is recorded. Historical data provides a variety of convenient and fast ways to query.
4.6 power function
When the main power supply has a power failure, undervoltage, etc., the monitoring equipment can automatically switch to the standby power supply. When the main power supply returns to normal power supply, it automatically switches back to the main power supply, ensuring continuous and smooth operation of the monitoring equipment during the switching process.
4.7 pairs of detector control functions
Through the system software operation, all the detectors connected to the device can be remotely controlled, including the setting of alarm setting value, communication address and other parameters and remote reset of the detector.
4.8 permission control function
In order to ensure the safe operation of the monitoring system, the operating authority of the monitoring device system software is divided into three levels, and operators of different levels have different operating rights.
5 Conclusion
The electrical fire monitoring system of the Suzhou North Ring Road Tunnel consists of the electrical fire monitoring device Acrel-6000 and the leakage fire detector ARCM100-Z. The Acrel-6000 electrical fire monitoring system is an industrial grade that is independently developed by the company to receive field devices such as residual current electrical fire detectors to achieve alarm, monitoring, control, and management of protected electrical circuits. Hardware/software system. The system is applied to the fire control center of large shopping malls, living quarters, production bases, office buildings, shopping malls and other areas, and telemetry, remote adjustment, remote control and remote signaling of detectors scattered in the building are convenient for monitoring and management. The system uses a standard Modbus field bus to connect detectors with communication functions. When the detected parameter in the field protection circuit exceeds the alarm set value, it can send out alarm signals and control signals, can indicate the alarm part and save the alarm. information. The field instrument is connected to the Acrel-6000 piano electrical fire monitoring system of the control center by bus. The system has the advantages of convenient installation and transportation, high cost performance and convenient maintenance. The application of Acrel-6000 electrical fire monitoring system in Suzhou Beihuan auxiliary road tunnel, real-time monitoring of leakage current of various power circuits on the site, sound and light alarm for loops with abnormal conditions, timely reminding on-site duty personnel to ensure safe and reliable power supply. And to avoid the loss of field equipment and casualties.
references
[1]. Ren Zhicheng Zhou Zhong. Principles and Application Guidelines of Power Electrical Measurement Digital Instrumentation [M]. Beijing. China Electric Power Press. 2007. 4
[2]. Zhou Zhong. Application of power meter in electric energy metering of large public buildings [J]. Modern Building Electric 2010. 6
About the author: Yang Junjun, female, undergraduate. Currently working for Ankerui Electric Co., Ltd., contact number, mobile phone, QQ
Http://news.chinawj.com.cn Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn
Yang Junjun An Kerui Electric Co., Ltd. Shanghai Jiading
Summary:
0 Overview
The Suzhou North Ring Tunnel is located at the South Square of Suzhou Railway Station. The total length of the project is 928.75 meters, of which the tunnel is 725 meters long and the construction cost is about 180 million yuan. The scope of monitoring of this project is a basement substation.
There are 159 ARCM100-Z residual current meters in the R&D building of Suzhou Printing Factory, which are installed in the floor distribution box. The field instrument is connected to the Acrel-6000 piano electrical fire monitoring system of the control center by bus.
1 reference standard
In recent years, in order to increase the intensity of electrical fire monitoring and prevention, the state has successively formulated or revised a number of relevant standards and regulations to strengthen the prevention of electrical fires. There are:
1. It is GB50045-95 (2005 edition) "Code for Fire Protection Design of High-rise Civil Buildings", which stipulates in Article 9.5.1 that it is necessary to install a leakage fire alarm system in places with high fire risk and dense personnel in high-rise buildings.
2. It is GB50016-2006 "Code for Fire Protection of Building Design", which is stipulated in Article 11.2.7: The following places should be equipped with residual current action electrical fire monitoring system. These venues include various types of theaters, galleries, warehouses, residential communities, hospitals, shops, schools, and more.
3. The relevant provisions of the national standard "Building electrical fire prevention requirements and testing methods" also clearly require that "the residual current action protector that automatically cuts off the power or alarm should be set at the power incoming end".
4. The products of the electrical fire monitoring system shall meet: GB14287.1-2005 "Electrical Fire Monitoring Equipment", GB14287.2-2005 "Residual Current Electric Fire Monitoring Detector", GB14287.3-2005 "Measurement Temperature Electric Fire Monitoring and Detection" 》
5. The installation and operation of the electrical fire monitoring system shall meet the requirements of GB13955-2005 "Installation and operation of residual current action protection device"
6. The power supply of the electrical fire monitoring system shall meet the requirements of GB50052 "Design Specifications for Power Supply and Distribution Systems"
7. The design of the electrical fire monitoring system shall meet the requirements of the Design Method of Electrical Fire Monitoring System (Interim Provisions)
2 system components
The electrical fire project of Suzhou North Ring Road Tunnel consists of electrical fire monitoring background, electrical fire detector and leakage current transformer.
The communication bus of this project has access to eight communication buses, which are respectively connected to the distribution outlets of the power distribution station and are connected to the corresponding buses. After the bus is connected hand in hand in a distribution box, it is connected to the background of the piano to form the aorta of the electrical fire system. The leakage current transformer in the drawer cabinet is connected to the leakage detector through the current line, and the leakage detector displays the leakage condition in real time. The above describes a set of electrical fire monitoring systems with stable signal and reliable accuracy. The system networking is divided into three layers:
1) Station management
The management of the station control management system for the electrical fire monitoring system is the direct window of human-computer interaction and the uppermost part of the system. Mainly consists of system software and necessary hardware equipment, such as console, UPS power supply and so on. The monitoring system software calculates, analyzes, and processes various types of data information on the site, and responds to the on-site transportation situation by means of graphics, digital display, sound, and indicator lights.
Monitoring host: used for data collection, processing, and data forwarding. Provides data interfaces for system management, maintenance, and analysis within and outside the system.
UPS: Ensure the normal power supply of the computer monitoring system, and ensure the normal operation of the station management management equipment when the whole system has power supply problems.
The background monitoring device is set in the basement control room.
2) Network communication layer
Communication medium: The system mainly adopts shielded twisted pair cable, realizes real-time communication between field device and host computer by RS485 interface and MODBUS communication protocol.
3) Field device layer
The field device layer is a data acquisition terminal, mainly for the ARCM100-Z series of residual electrical fire monitoring detectors.
The system structure topology is as follows:
3 electrical fire equipment
3.1 Main equipment parameters:
a power supply
1 rated working voltage AC220V (-15% ~ +10%)
2 Backup power supply: When the main power supply is under voltage or power failure, maintain the monitoring equipment working time ≥ 30 minutes
b work system
24-hour work schedule
c communication method
RS485 bus communication, Modbus-RTU communication protocol, transmission distance of 1km, can extend the communication transmission distance through the repeater.
d monitoring capacity
1 The monitoring device can monitor up to 1024 monitoring units (detectors).
2 can be equipped with ARCM series monitoring detectors.
e monitoring alarm project
1 Residual current fault (leakage): fault unit attribute (part, type)
2 Temperature alarm (over temperature): Fault unit attribute (part, type)
3 Current fault (overcurrent): Fault unit attribute (part, type)
Monitoring alarm response time: ≤30s
Monitoring alarm sound pressure level (A weighting): ≥70db/1m
Monitoring alarm light display: red LED indicator
Monitor alarm sound signal: Manually cancel, when the alarm signal is input again, it can be started again
f fault alarm item
1 The connection between the monitoring device and the detector is open and shorted.
2 main power undervoltage or power failure
3 standby power battery short circuit, open circuit
Fault alarm response time: ≤100s
Monitoring alarm sound pressure level (A weighting): ≥70db/1m
Monitoring alarm light display: yellow LED indicator
Fault alarm sound signal: manual elimination, can be started again when there is alarm signal input again
The normal operation of the non-faulty loop is not affected during the fault
g control output
Alarm control output: normally open passive contact, capacity: AC250V 3A or DC30V 3A
h self-test project
1 Indicator check: alarm, fault, operation, main power, standby power indicator
2 monitor check
3 audio device inspection
Self-test time ≤60s
i history
1 Record content: record type, time of occurrence, detector, area, fault description.
2 Record query: Query according to the date and type of the record.
j operation rating
1 Daily duty class: real-time status monitoring, history query.
2 Monitoring operation level: real-time status monitoring, history query, remote reset of detector.
3 System management level: real-time status monitoring, history query, remote reset of detectors, remote modification of detector parameters, system parameter setting and modification of monitoring equipment, operator addition and deletion.
k use environmental conditions
1 Workplace: Fire control room, or installed side by side with fire control console
2 Working environment temperature: 0 ° C ~ 40 ° C
3 Working environment relative humidity: 5% ~ 95% RH
4 Altitude: ≤2500m
l main components
1 main control unit: industrial grade computer (CPU frequency is not lower than 2.0G, 1G and above memory), configuration keyboard, mouse and 17" liquid crystal display;
2 I/O modules: built-in ARTU remote intelligent I/O modules developed by the company;
3 sound and light alarm: built-in active speakers, LED indicators;
4 button: mute button, reset button;
5 Backup power supply: built-in 1kVA online long-acting UPS, 3 12V/24Ah maintenance-free batteries.
3.2, ARCM300 series instruments
The ARCM300 residual current electrical fire monitoring detector is designed for TT and TN systems below 0.4kV. It monitors and manages fire risk parameters such as residual current, conductor temperature, overcurrent and overvoltage in the distribution circuit. Thereby preventing the occurrence of electrical fires and real-time monitoring of various power parameters, providing accurate data for energy management. The product adopts advanced microcontroller technology, with high integration, small size, convenient installation, intelligent, digital and networked. It is an ideal choice for building electrical fire prevention monitoring and system insulation aging prediction. The product complies with the standard requirements of GB14287.2-2005 "Electrical Fire Monitoring System Part 2: Residual Current Electrical Fire Monitoring Detector".
4 system function
4.1 monitoring alarm function
The monitoring equipment can receive the leakage and temperature information of multiple detectors, and emit an audible and visual alarm signal when the alarm occurs. At the same time, the red “alarm†indicator on the cabinet lights up. The display indicates the alarm part and leakage, temperature value, record alarm time, sound and light alarm. Keep it until the detector is reset remotely by pressing the Reset button. The audible alarm signal can also be manually removed using the mute button.
4.2 control output function
When the monitored loop leakage alarm, the control output relay is closed to control the protected circuit or other equipment. When the alarm is eliminated, the control output relay is released.
4.3 fault alarm function
Communication failure alarm: When a communication failure occurs between the monitoring device and any of the connected detectors, the corresponding detector in the monitoring screen displays a fault indication, and the yellow “fault†indicator on the cabinet lights up, and a fault alarm sound is emitted. .
Power failure alarm: When the main power or backup power fails, the monitoring device also emits an audible and visual alarm signal and displays the fault information. You can enter the corresponding interface to view the detailed information and release the alarm sound.
4.4 self-test function
Check that all status indicators, displays, and audio devices in the device are working.
4.5 alarm record storage query function
When leakage, over-temperature alarm or communication or power failure occurs, the alarm part, fault information, alarm time and other information are stored in the database. When the alarm is cancelled or the fault is eliminated, the same is recorded. Historical data provides a variety of convenient and fast ways to query.
4.6 power function
When the main power supply has a power failure, undervoltage, etc., the monitoring equipment can automatically switch to the standby power supply. When the main power supply returns to normal power supply, it automatically switches back to the main power supply, ensuring continuous and smooth operation of the monitoring equipment during the switching process.
4.7 pairs of detector control functions
Through the system software operation, all the detectors connected to the device can be remotely controlled, including the setting of alarm setting value, communication address and other parameters and remote reset of the detector.
4.8 permission control function
In order to ensure the safe operation of the monitoring system, the operating authority of the monitoring device system software is divided into three levels, and operators of different levels have different operating rights.
5 Conclusion
The electrical fire monitoring system of the Suzhou North Ring Road Tunnel consists of the electrical fire monitoring device Acrel-6000 and the leakage fire detector ARCM100-Z. The Acrel-6000 electrical fire monitoring system is an industrial grade that is independently developed by the company to receive field devices such as residual current electrical fire detectors to achieve alarm, monitoring, control, and management of protected electrical circuits. Hardware/software system. The system is applied to the fire control center of large shopping malls, living quarters, production bases, office buildings, shopping malls and other areas, and telemetry, remote adjustment, remote control and remote signaling of detectors scattered in the building are convenient for monitoring and management. The system uses a standard Modbus field bus to connect detectors with communication functions. When the detected parameter in the field protection circuit exceeds the alarm set value, it can send out alarm signals and control signals, can indicate the alarm part and save the alarm. information. The field instrument is connected to the Acrel-6000 piano electrical fire monitoring system of the control center by bus. The system has the advantages of convenient installation and transportation, high cost performance and convenient maintenance. The application of Acrel-6000 electrical fire monitoring system in Suzhou Beihuan auxiliary road tunnel, real-time monitoring of leakage current of various power circuits on the site, sound and light alarm for loops with abnormal conditions, timely reminding on-site duty personnel to ensure safe and reliable power supply. And to avoid the loss of field equipment and casualties.
references
[1]. Ren Zhicheng Zhou Zhong. Principles and Application Guidelines of Power Electrical Measurement Digital Instrumentation [M]. Beijing. China Electric Power Press. 2007. 4
[2]. Zhou Zhong. Application of power meter in electric energy metering of large public buildings [J]. Modern Building Electric 2010. 6
About the author: Yang Junjun, female, undergraduate. Currently working for Ankerui Electric Co., Ltd., contact number, mobile phone, QQ
Http://news.chinawj.com.cn Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn
100 Feet Photoluminescent Exit Sign
Luminescent Signage,100 Feet Photoluminescent Exit Sign,Afterglow Super Sign,Afterglow Tape
JINAN REALGLOW CO.,LTD , https://www.realglowsign.com